operating: | -40° to 160°F (-40° to 70°C) |
operating: | 5-95% R.H |
Refer to this table to determine maximum wire lengths allowed.
18 AWG | |
equipment interface to sensor module | 1000ft / 380m |
sensor module to sensors | 250ft / 39m |
Honeywell | C7189U indoor sensor |
C7089U outdoor sensor | |
Tekmar | D076 indoor sensor |
D079 slab sensor | |
D084 flush mount sensor | |
Johnson Controls | HT-6703 humidity sensor |
CD-W00 CO2 sensor |
Other temperature sensors can be supported by just entering the B value or the resistance
reported by the sensor at 70°F (21°C) during the configuration process.
R1 | R2 | R3 | R4 | |
dry contacts | yes | yes | yes | yes |
temperature 10KΩ NTC resistive |
yes | yes | yes | yes |
Humidity or CO2 0-10 or 0-5 Vdc |
no | no | yes | yes |
Humidity or CO2 0-10 or 0-5 Vdc |
no | no | yes | yes |